UL fire Pipe

UL Fire Pipe
UL Fire Pipe, also known as a standpipe, is a specialized pipe designed exclusively for firefighting applications. Made from robust materials that can withstand high temperatures and pressures, it’s the preferred choice for many commercial and industrial buildings worldwide. These pipes undergo rigorous testing and inspection by UL, an independent safety organization, ensuring they meet the highest safety and performance standards. Furthermore, our UL Fire Pipe is equipped with unique fittings for quick connections to fire hoses and other firefighting equipment. At UNIACERO, we prioritize safety, and our UL Fire Pipe is a testament to our commitment.
UL Fire Pipe Specification
Our UL Fire Pipe is available in a range of coatings, including galvanizing, FBE, and varnish coatings, each offering distinct advantages. With a coating thickness ranging from 250 microns to 550 microns, our pipes are designed to resist corrosion, UV rays, and chemicals. They operate efficiently in temperatures ranging from -30°C to 80°C and can handle pressures from 0.1 Mpa to 0.25 Mpa. Whether you need threaded, grooved, flanged, or welded connections, we have you covered. Trust UNIACERO for unmatched quality and durability.
| Certificate : | UL852 Listed | |
| Material: | ASTM Standards or other nationally or internationally recognized pipe standards. | |
| Pipe End : | PE | Thread |
| Grooved | – | |
| Anti-corrosion Treatment: | Black | Galvanized |
| Epoxy | Red Prime | |
| Diameter: | 1/2, 3/4, 1, 1-1/4, 1-1/2, 2, 2-1/2, 3,4, 6, 8, 10 ,12,14 and 16 in | |
| Wall Thickness: | SCH5,SCH10,SCH30,SCH40 | |
| Pipe Pressure Rating: | ≥175 psi(1206KPa) | |
| Test: | Bending Moment Tests | Fire Test |
| Leakage Test | Materials Test | |
| Hydrostatic Test | Tensile Test | |
| Vibration Test | – | |
| Marking: | Manufacturer’s name, private labeler’s name,or identifying symbol | |
| Model designation, Schedule, or wall thickness | ||
| Nominal pipe size | ||
| Rated pressure | ||
| Corrosion Resistance Ratioa″or ″CRR″For Threaded Pipe,WT≤SCH40 and Unthreaded Pipe,WT≤SCH10, | ||
| The hydrostatic test pressure or ″NDE″ | ||
| For WT≤SCH40 ,pipe is intended to be threaded,the following statement will be marked:”CAUTION: IMPROPER THREADING MAY LEAD TO LEAKING. CHECK ALL THREADS WITH ANSI B1.20.1 THREAD GAUGE. | ||
UL Fire Pipe Dimension Table

Our UL Fire Pipes are available in sizes ranging from DN15 to DN1200, ensuring that we cater to diverse requirements. Each dimension is meticulously crafted, ensuring seamless integration into any firefighting system. When you choose UNIACERO, you’re not just getting a product; you’re investing in precision.
| N.D. | O.D. | SCH 10 | SCH 30/40 | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| WALL THICKNESS | NOMINAL WEIGHT | WALL THICKNESS | NOMINAL WEIGHT | ||||||||
| (mm) | (inch) | (mm) | (inch) | (mm) | (inch) | (kg/mtrs) | (lbs/ft) | (mm) | (inch) | (kg/mtrs) | (lbs/ft) |
| 15 | 1/2 | 21.3 | 0.84 | —- | —- | —- | —- | 2.77 | 0.109 | 1.27 | 0.85 |
| 20 | 3/4 | 26.7 | 1.05 | 2.11 | 0.083 | 1.28 | 0.96 | 2.87 | 0.113 | 1.69 | 1.13 |
| 25 | 1 | 33.4 | 1.32 | 2.77 | 0.109 | 2.09 | 1.41 | 3.38 | 0.133 | 2.5 | 1.68 |
| 32 | 1-1/4 | 42.2 | 1.66 | 2.77 | 0.109 | 2.69 | 1.81 | 3.56 | 0.14 | 3.39 | 2.27 |
| 40 | 1-1/2 | 48.3 | 1.9 | 2.77 | 0.109 | 3.11 | 2.09 | 3.68 | 0.145 | 4.05 | 2.72 |
| 50 | 2 | 60.3 | 2.38 | 2.77 | 0.109 | 3.93 | 2.64 | 3.91 | 0.154 | 5.45 | 3.66 |
| 65 | 2-1/2 | 73 | 2.88 | 3.05 | 0.12 | 5.26 | 3.53 | 5.16 | 0.203 | 8.64 | 5.8 |
| 80 | 3 | 88.9 | 3.5 | 3.05 | 0.12 | 6.46 | 4.34 | 5.49 | 0.216 | 11.29 | 7.58 |
| 90 | 3-1/2 | 101.6 | 4 | 3.05 | 0.12 | 7.41 | 4.98 | 5.74 | 0.226 | 13.58 | 9.12 |
| 100 | 4 | 114.3 | 4.5 | 3.05 | 0.12 | 8.37 | 5.62 | 6.02 | 0.237 | 16.09 | 10.8 |
| 125 | 5 | 141.3 | 5.56 | 3.4 | 0.134 | 11.58 | 7.78 | 6.55 | 0.258 | 21.79 | 14.63 |
| 150 | 6 | 168.3 | 6.63 | 3.4 | 0.134 | 13.85 | 9.3 | 7.11 | 0.28 | 28.29 | 18.99 |
| 200 | 8 | 219.1 | 8.63 | 4.78 | 0.188 | 25.26 | 16.96 | 7.04 | 0.277 | 36.82 | 24.72 |
| 250 | 10 | 273.1 | 10.75 | 4.78 | 0.188 | 31.62 | 21.23 | 7.08 | 0.307 | 51.05 | 34.27 |
Chemical Requirements of UL Fire Pipe
Our UL Fire Pipes are crafted from materials that are resistant to various chemicals, ensuring longevity and performance. The chemical composition is meticulously balanced, ensuring that the pipes remain unaffected by the harsh elements they might be exposed to during their lifecycle.
| Elements | Grade A | Grade B | Grade C |
| Carbon max. % | 0.25 | 0.3 | 0.35 |
| Manganese % | 0.27 to 0.93 | 0.29 to 1.06 | 0.29 to 1.06 |
| Phosphorous, max. % | 0.025 | 0.025 | 0.025 |
| Sulfur, max. % | 0.025 | 0.025 | 0.025 |
| Silicon, min. % | 0.1 | 0.1 | 0.1 |
Mechanical Requirements of UL Fire Pipe
At UNIACERO, we understand the importance of mechanical strength. Our UL Fire Pipes are designed to withstand high pressures and temperatures without compromising on flexibility. This balance ensures that our pipes can be easily installed while still providing the robustness required for firefighting applications.
| Grade A | Grade B | Grade C | |
| Tensile Strength, min., psi | 48,000 | 60,000 | 70,000 |
| Yield Strength, min., psi | 30,000 | 35,000 | 40,000 |